Thank you for visiting!
Our website is being updated.

F35 – 1 (35kVA)

Specifications:

Output Ratings
Voltage , Frequency Prime Standby
400V , 50 Hz 32 kVA / 25.6  kW 9.5 kVA / 7.6 kW
–         / – –         / –

Ratings at 0.8 power factor.

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Standard Reference Conditions

Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

Ratings ang Performance Data
Engine Make & Model : Perkins FD4  – 3.9A1
Alter manufactured for FG Wilson by : Marelli
Alternator model : MJB 160 MB4
Control Panel : DCP – 10
Base Frame : Heavy Duty Fabricated steel
Circuit Breaker Type : 3 Pole MCB
Frequency : 50 Hz 60 Hz
Engine Speed : RPM 1500 1800
Fuel Tank Capacity :

Litres (US gal)

145 (38.3)
Fuel Consumption : l/hr (US gal/hr)

(100% Load)                                 – Prime

–         Standby

 

9.4 (2.5)

10.0 (2.6)

 

 

Available Options
FG Wilson ofer a range of optional features to tailor our generating sets to meet your power needs . Options include:

·        Upgrade to CE Certification

·        A wide range of Sound Attenuated Enclosures

·        A variety og generating set control panels

·        Additional alarms and shutdowns

For futher information on all of the standard and optional features accompanying this product please contact your local Dealer or visit : www.FGWilson.com

 

Dimensions and weights
Length (L)

mm (in)

With (W)

mm (in)

Height (H)

mm (in)

Dry

Kg (Ib)

Wet

Kg (Ib)

1680 (66.1) 760 (29.9) 1273 (49.2) 724 (1596) 736 (1623)
Dry = With Lube Oil                     Wet = With Lube Oil and Coolant

 

Engine Technial Data
No. of Cylinders / Alignment 4 / In Line
Cycle 4 Stroke
Bore / Stroke : mm (in) 102.0 (4.0) / 118.0 (4.6)
Induction : Naturally Aspirated
Cooling Method: Water
Governing Type Electronic
Governing Class ISO 8528 G2
Compression Ratio : 18:1
Displacement :I (cu.  in) 3.9 (235.6)
Moment of Inertia: kg m2 (Ib/in2)
Engine Electrical System:

-Voltage / Ground

-Battery Charger Amps

 

12/Negative
54

Weight : kg(Ib)            – Dry

-Wet

300 (661)

325 (716)

 

Performance 50 Hz 60 Hz
Engine Speed : rpm 1500
Gross Engine Power : kW (hp)

-Prime

-Standardby

 

33.0 (44.0)

35.0 (47.0)

 

BMEP : kPa (psi)

-Prime

-Standardby

 

685.0 (99.3)

726.0(105.3)

 

 

Fuel System
Fuel Filter Type Spin On
Recommended Fuel : Class A2 Diesel or BSEN590
Fuel Consumption : l/hr (US gal/hr)
 

Prime

110%

Load

100%

Load

75%

Load

50%

Load

50 Hz 10.0 (2.6) 9.4 (2.5) 7.0 (1.8) 4.9 (1.3)
60 Hz
 

Standby

100%

Load

75%

Load

50%

Load

50 Hz 10.0 (2.6) 7.6 (2.0) 5.2 (1.4)
60 Hz

 

Air Systems 50 Hz 60 Hz
Air Filter Type : Replaceable Element
Combustion Air Flow : m3/min (cfm)

-Prime

-Standardby

 

2.8 (97)

 

Max. Combustion Air Intake

Restriction : kPa (in H2O)

 

5.0 (20.1 )

 

 

Cooling System 50 Hz 60 Hz
Cooling System Capacity : I (US gal) 12.0 (3.2)
Water Pump Type : Centrifugal
Heat Rejected to Water & Lube Oil :

 kW (Btu/ min)                                 -Prime

-Standardby

 

 

Heat Radiation to Rom : Heat radiated from engine and altemator

kW (Btu/ min)                                 -Prime

-Standardby

 

 

 

Radiator Fan Load : kW (hp) 1.4 (1.9)
Radiator Cooling Airflow : m3/min (cfm) 66.0 (2331)
External Restriction to

Cooling Airflow : Pa (in H2O)

 

125 (0.5)

 

 

Lubrication System
Oil Filter Type : Spin – On , Full Flow
Total Oil Capacity : I (US gal) 8.5 (2.2)
Oil Pan : I (US gal)
Oil Type : 15W – 40CD
Oil Cooling Method: Water

 

Exhaust System 50 Hz 60 Hz
Maximum Allowable Back Pressure : kPa (in Hg) 6.5 (1.9)
Exhaust Gas Flow : m3/min (cfm)

-Prime

-Standardby

 

8.3 (292)

 

Exhaust Gas Temperature : oC( oF)

-Prime

-Standardby

 

 

 

Alternator Physical Data
Manufactured for FG Wilson by: Marelli
Model : MJB 160 MB4
No . of Bearings : 1
Insulation Class : H
Winding Pitch Code 2/3 – M0
Wires : 12
Ingress protection Rating : IP23
Eccitation System : SHUNT
AVR Model : Mark V

 

Alternator Operating Data
Overspeed : rpm 2250
Voltage Reguation : (steady state) + / – 1.0%
Wave Form NEMA = TIF 50
Wave Form IEC = THF 2.0%
Total Harmonic content LL/LN 2.0%
Radio Interference : Suppression is in line with European

Standard EN61000 – 6

Radiant Heat : kW (Btu/min)

-50Hz

– 60Hz

 

4.0 (227)

 

Alternator

Performance Data

50 Hz 60 Hz
Data Item 415/240V 400/230V 380/220V
Motor Starting

Capability*kVA

 

52

 

48

 

43

Short Circuit

Capacity %

Reactances : Per Unit

Xd

X’d

X”d

 

2.546

0.232

0.099

 

2.740

0.250

0.107

 

2.932

0.267

0.114

 

Output Ratings Technical Data 50Hz
Voltage Prime: Standby:
kVA kW kVA kW
415/240V 32.0 25.6 35.0 28.0
400/230V 32.0 25.6 35.0 28.0
380/220V 30.9 24.7 34.0 27.2
Output Ratings Technical Data 60Hz
Voltage Prime: Standby:
kVA kW kVA kW

Detail Information:

https://www.fgwilson.com/cda/files/4634926/7/F35-1%20GB%20(0814).pdf

https://www.fgwilson.com/cda/files/4634951/7/35-125%20kVA%20CAL%20CALG%20Enclosure(GB).pdftopodwebsites for escortsрадиатор нижняя подводка

Overview


F-Model

Features


Benefits


Default backup time

Customer Support: (08) 38.420.458

Head Office

219 Nguyen Dinh Chinh, Ward 11,
Phu Nhuan Dist, Ho Chi Minh City, Vietnam.
Tel: (+84)8.38.420.458 - Fax: (+84).8.38.420.459
Hotline: 0938.805.380 (Mr.Tuấn)

Representative Office

Room 402, 85 Nguyen Chi Thanh,
Dong Da Dist, Hanoi, Vietnam
Tel: (+84)4.35.668.011 - Fax: (+84)4.35.668.030