Specifications:
Output Ratings | ||
Voltage , Frequency | Prime | Standby |
230V , 50 Hz | 350.0 kVA / 280.0 kVW | 400.0 kVA / 320.0 kW |
240/120V , 60 HZ | -/- | -/- |
Ratings at 0.8 power factor.
Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Ratings ang Performance Data | ||
Engine Make & Model : | Perkins 2206A – E13TAG2 | |
Alter manufactured for FG Wilson by : | Leroy Somer | |
Alternator model : | LLB16114B | |
Control Panel : | PwerWizard 1.1 + | |
Base Frame : | Heavy Duty Fabricated steel | |
Circuit Breaker Type : | 3 Pole MCB | |
Frequency : | 50 Hz | 60 Hz |
Engine Speed : RPM | 1500 | 1800 |
Fuel Tank Capacity :Litres (US gal) | 888 (234.6) | |
Fuel Consumption : l/hr (US gal/hr) (100% Load) – Prime
– Standby |
69.6 (18.4)
79.0 (20.9) |
–
– |
Available Options |
FG Wilson ofer a range of optional features to tailor our generating sets to meet your power needs . Options include:· Upgrade to CE Certification
· A wide range of Sound Attenuated Enclosures · A variety og generating set control panels · Additional alarms and shutdowns For futher information on all of the standard and optional features accompanying this product please contact your local Dealer or visit : www.FGWilson.com |
Dimensions and weights | |||
With (W)mm (in) | Height (H)mm (in) | DryKg (Ib) | |
1131 (44.5) | 2156 (84.9) | 3183 (7017) | |
Dry = With Lube Oil Wet = With Lube Oil and Coolant |
Engine Technial Data | |
No. of Cylinders / Alignment | 6 / In Line |
Cycle | 4 Stroke |
Bore / Stroke : mm (in) | 130.0 (5.1) / 157.0 (6.2) |
Induction : | Turbocharged Air To Air Charge Cooled |
Cooling Method: | Water |
Governing Type | Electronic |
Governing Class | ISO 8528 G2 |
Compression Ratio : | 16.3 :1 |
Displacement :I (cu. in) | 2.77 (9465) |
Moment of Inertia: kg m2 (Ib/in2) | 1.14 (3896) |
Engine Electrical System:-Voltage / Ground
-Battery Charger Amps |
24/Negative 70 |
Weight : kg(Ib) – Dry-Wet | 1301 (2868)1351 (2978) |
Performance | 50 Hz | 60 Hz |
Engine Speed : rpm | 1500 | – |
Gross Engine Power : kW (hp)-Prime
-Standardby |
324.2 (435.0)
367.4 (493.0) |
–
– |
BMEP : kPa (psi)-Prime
-Standardby |
2075.0 (300.9)
2350.0 (340.9) |
–
– |
Fuel System | |
Fuel Filter Type | Replaceable Element |
Recommended Fuel : | Class A2 Diesel or BSEN590 |
Fuel Consumption : l/hr (US gal/hr) |
Default backup time
Customer Support: (08) 38.420.458
219 Nguyen Dinh Chinh, Ward 11,
Phu Nhuan Dist, Ho Chi Minh City, Vietnam.
Tel: (+84)8.38.420.458 - Fax: (+84).8.38.420.459
Hotline: 0938.805.380 (Mr.Tuấn)
Room 402, 85 Nguyen Chi Thanh,
Dong Da Dist, Hanoi, Vietnam
Tel: (+84)4.35.668.011 - Fax: (+84)4.35.668.030